Open Plan Room | Original | / | 2/3/2015 | SHARONOVAO | SHARONOVAO | Path 2 Location = Open Plan Room by SHARONOVAO | | Open Plan Room | 9712 |
Open Plan Room | Original | / | 2/3/2015 | SHARONOVAO | SHARONOVAO | Path 1 Location = Open Plan Room by SHARONOVAO | | Open Plan Room | 9711 |
Mechanical | Original | A | 2/3/2015 | SHARONOVAO | SHARONOVAO | per Gil the B.O. | | Mechanical | 9710 |
Env. Health | Original | A | 2/3/2015 | DOUSSETTA | DOUSSETTA | Good Morning, Aaron ; Thank you for taking the time to speak with me this morning regarding the issues my contractor is having with getting a building permit to refurbish the above mentioned property, more specifically Teller County Environmental Health’s notation to that properties file Good Morning, Aaron; Thank you for taking the time to speak with me this morning regarding the issues my contractor is having with getting a building permit to refurbish the above mentioned property, more specifically Teller County Environmental Health’s notation to that properties file concerning the underground gas tanks that were once located there .
As we discussed, the previous owner had the gas tanks removed in 2014 and is fully responsible for everything pertaining to those tanks, more than likely until such time as all state requirements are met. I have attached an executed copy of the Environmental and Hazardous Substances Indemnity Agreement between the previous owner and Mr. Kuyper which I hope will be sufficient documentation for Teller County Environmental Health to feel that the gas tank issue is being addressed and is now solely in the hands of the previous owner and the State of Colorado and will recommend releasing the requested building permits to refurbish the structure.
Please let me know if you have any additional comments, questions, or concerns regarding the gas tanks previously located at 11102 W US Hwy 24, Divide, CO 80814.
Thank you for your time regarding this matter and helping ensure that Teller Region has and will always remain a safe and beautiful place for people to live, work and recreate.
Sincerely,
Bryan Johnson PK Enterprises, Inc. PO Box 729 Divide, CO 80814 Phone: 719-687-6011 Ext: 23 Fax: 719-687-6788 | | Env. Health | 9706 |
County Zoning | Original | A | 1/20/2015 | PELLEGRINOL | PELLEGRINOL | Complies with C-1 zone. Within Growth Area. Hwy 24 boundary considered front yard (10' setback), everything else is side yard (zero setback). Parking to comply with submitted site plan. Non-impervious area (minimum 20% of lot) to be seeded prior to final structural approval per site plan. | | County Zoning | 9655 |
Fire | Original | N | 1/15/2015 | SHARONOVAO | SHARONOVAO | Per Vernon Champlin | | Fire | 9643 |
Construction | Original | A | 1/12/2015 | SHARONOVAO | SHARONOVAO | no change in occupancy, egress, or interior configuration. Small interior remodel. ---OK | | Construction | 9631 |
Env. Health | Original | D | 1/12/2015 | SHARONOVAO | SHARONOVAO | Note from EH: If this property is to be used for anything other than a service station, please have the owner call the division of oil safety to determine if there are any requirements for the abandonment of the underground storage tanks. 303-318-8547
Provide a copy of the removal permit from the State to Environmental Officer ASAP. | | Env. Health | 9630 |
Roads & Bridges | Original | N | 1/12/2015 | SHARONOVAO | SHARONOVAO | per Bryan see notes | | Roads & Bridges | 9627 |
Plumbing | Original | N | 1/12/2015 | SHARONOVAO | SHARONOVAO | | | Plumbing | 9624 |
Mechanical | Original | D | 1/12/2015 | SHARONOVAO | SHARONOVAO | PLAN REVIEW CORRECTIONS NOTICE
PERMIT #: 12022 ADDRESS: 11102 W HWY 24 PROJECT NAME: DIVIDE INVESTMENT PROPERTIES DATE OF REVIEW: 01`/12/2015 PLANS EXAMINER: Olya Sharonova sharonovao@co.teller.co.us SCOPE OF WORK: INTERIOR REMODEL STATUS: THE FOLLOWING CORRECTIONS ARE REQUESTED
PLEASE PROVIDE TWO COPIES OF THE FOLLOWING TO COMPLETE THE PLAN REVIEW PROCESS. A WRITTEN RESPONSE FOR EACH ITEM LISTED BELOW IS REQUIRED THAT SPECIFICALLY IDENTIFIES THE REVISION OR CORRECTION BEING MADE. BUBBLE OR HIGHLIGHT ALL REVISED DETAILS AND DRAWINGS ON NEWLY SUBMITTED PLAN SHEETS. IF THESE CORRECTION ITEMS ARE ON STAMPED PAGES THEY WILL REQUIRE THE DESIGN PROFESSIONAL OF THAT DISCIPLINE TO PROVIDE AND STAMP THESE NEW PAGES OF CORRECTIONS.
Please provide a letter addressing the fowling corrections:
? 1. Justify Ventilation Per 2009 IMC Table 403.3 and IBC section 406.6.3 also need to provide makeup air ? 2. Provide Source Capture System Per IBC 502.14
IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT (719) 686-5408, EMAIL ME OR CONTACT DAN , TO DISCUSS THE CONDITIONS OR SET UP AN APPOINTMENT TIME WHEN I CAN BE AVAILABLE TO MEET YOU AT THE COUNTER TO GO OVER THE PLANS.
Gil Anderson Teller County Building Official | | Mechanical | 9623 |
Electrical | Original | A | 1/12/2015 | SHARONOVAO | SHARONOVAO | see attached letter ok per Gil | | Electrical | 9621 |
County Zoning | Original | D | 12/15/2014 | PELLEGRINOL | PELLEGRINOL | Complies with C-1 zone. Hwy 24 boundary is front yard (10' setback), everything else is side yard (zero setback). Parking stalls to be provided per site plan. Construction/development/parking etc within easements (if any) must be approved by easement holder. Seeding for all non-impervious area to be in place and reviewed with final structural inspection. Final structural should not be approved without seeding in place. | | County Zoning | 9568 |
Mechanical | Original | N | 12/15/2014 | CORCORANC | CORCORANC | | | Mechanical | 9567 |
Electrical | Original | N | 12/15/2014 | CORCORANC | CORCORANC | | | Electrical | 9566 |
Roads & Bridges | Original | D | 12/15/2014 | CORCORANC | CORCORANC | Driveway(s) possibly, and we will need to see copy of any CDOT access permit(s) prior to issuing any dw permit. PER BRYAN | | Roads & Bridges | 9565 |
Electrical | Original | D | 12/15/2014 | SHARONOVAO | SHARONOVAO | PLAN REVIEW CORRECTIONS NOTICE
PERMIT #: 12022 ADDRESS: 11102 W HWY 24 PROJECT NAME: DIVIDE INVESTMENT PROPERTIES DATE OF REVIEW: 12/15/2014 PLANS EXAMINER: Olya Sharonova sharonovao@co.teller.co.us SCOPE OF WORK: INTERIOR REMODEL STATUS: THE FOLLOWING CORRECTIONS ARE REQUESTED
PLEASE PROVIDE TWO COPIES OF THE FOLLOWING TO COMPLETE THE PLAN REVIEW PROCESS. A WRITTEN RESPONSE FOR EACH ITEM LISTED BELOW IS REQUIRED THAT SPECIFICALLY IDENTIFIES THE REVISION OR CORRECTION BEING MADE. BUBBLE OR HIGHLIGHT ALL REVISED DETAILS AND DRAWINGS ON NEWLY SUBMITTED PLAN SHEETS. IF THESE CORRECTION ITEMS ARE ON STAMPED PAGES THEY WILL REQUIRE THE DESIGN PROFESSIONAL OF THAT DISCIPLINE TO PROVIDE AND STAMP THESE NEW PAGES OF CORRECTIONS.
Please provide a letter addressing the fowling corrections:
? 1. Justify Ventilation Per 2009 IMC Table 403.3 and IBC section 406.6.3 also need to provide makeup air ? 2. Provide Source Capture System Per IBC 502.14 ? 3. Provide four air changes per 2011 NEC Article 511
IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT (719) 686-5408, EMAIL ME OR CONTACT DAN , TO DISCUSS THE CONDITIONS OR SET UP AN APPOINTMENT TIME WHEN I CAN BE AVAILABLE TO MEET YOU AT THE COUNTER TO GO OVER THE PLANS.
Gil Anderson Teller County Building Official | | Electrical | 9562 |
Mechanical | Original | D | 12/15/2014 | SHARONOVAO | SHARONOVAO | PLAN REVIEW CORRECTIONS NOTICE
PERMIT #: 12022 ADDRESS: 11102 W HWY 24 PROJECT NAME: DIVIDE INVESTMENT PROPERTIES DATE OF REVIEW: 12/15/2014 PLANS EXAMINER: Olya Sharonova sharonovao@co.teller.co.us SCOPE OF WORK: INTERIOR REMODEL STATUS: THE FOLLOWING CORRECTIONS ARE REQUESTED
PLEASE PROVIDE TWO COPIES OF THE FOLLOWING TO COMPLETE THE PLAN REVIEW PROCESS. A WRITTEN RESPONSE FOR EACH ITEM LISTED BELOW IS REQUIRED THAT SPECIFICALLY IDENTIFIES THE REVISION OR CORRECTION BEING MADE. BUBBLE OR HIGHLIGHT ALL REVISED DETAILS AND DRAWINGS ON NEWLY SUBMITTED PLAN SHEETS. IF THESE CORRECTION ITEMS ARE ON STAMPED PAGES THEY WILL REQUIRE THE DESIGN PROFESSIONAL OF THAT DISCIPLINE TO PROVIDE AND STAMP THESE NEW PAGES OF CORRECTIONS.
Please provide a letter addressing the fowling corrections:
? 1. Justify Ventilation Per 2009 IMC Table 403.3 and IBC section 406.6.3 also need to provide makeup air ? 2. Provide Source Capture System Per IBC 502.14 ? 3. Provide four air changes per 2011 NEC Article 511
IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT (719) 686-5408, EMAIL ME OR CONTACT DAN , TO DISCUSS THE CONDITIONS OR SET UP AN APPOINTMENT TIME WHEN I CAN BE AVAILABLE TO MEET YOU AT THE COUNTER TO GO OVER THE PLANS.
Gil Anderson Teller County Building Official | | Mechanical | 9561 |