Open Plan Room | Original | / | 6/4/2013 | SHARONOVAO | SHARONOVAO | Location = Open Plan Room by SHARONOVAO | | Open Plan Room | 5761 | Env. Health | Original | A | 6/4/2013 | DOUSSETTA | DOUSSETTA | Final approval pending opening inspection from EH. AD | | Env. Health | 5760 | Electrical | Original | A | 6/4/2013 | SHARONOVAO | SHARONOVAO | per Dan | | Electrical | 5758 | Env. Health | Original | D | 5/30/2013 | DOUSSETTA | DOUSSETTA | Food License has not been issued. Still pending approval. AD | | Env. Health | 5710 | Plumbing | Original | A | 5/24/2013 | SHARONOVAO | SHARONOVAO | with conditions see compliance permit A45345, the existing work will be inspected with new permit pulled as soon as building permit issued per Mark | | Plumbing | 5682 | Mechanical | Original | A | 5/24/2013 | SHARONOVAO | SHARONOVAO | with conditions see compliance permit A45345, the existing work will be inspected with new permit pulled as soon as building permit issued per Mark | | Mechanical | 5681 | Construction | Original | A | 5/24/2013 | SHARONOVAO | SHARONOVAO | with comments, see plans | | Construction | 5680 | NETC Fire | Original | N | 5/24/2013 | SHARONOVAO | SHARONOVAO | Per Vernon Champlin with Northeast Teller County Fire Protection District , with comments, see plans | | NETC Fire | 5679 | Electrical | Original | D | 5/20/2013 | SHARONOVAO | SHARONOVAO | PLAN REVIEW CORRECTIONS NOTICE
PERMIT #: 11261 ADDRESS: 800 RESEARCH DR. 250/260 PROJECT NAME: DYNAMIC TRAINING & FITNESS DATE OF REVIEW: 05/20/2013 PLANS EXAMINER: Olya Sharonova sharonovao@co.teller.co.us SCOPE OF WORK: TENANT FINISH STATUS: THE FOLLOWING CORRECTIONS ARE REQUESTED
PLEASE PROVIDE TWO COPIES OF THE FOLLOWING TO COMPLETE THE PLAN REVIEW PROCESS. A WRITTEN RESPONSE FOR EACH ITEM LISTED BELOW IS REQUIRED THAT SPECIFICALLY IDENTIFIES THE REVISION OR CORRECTION BEING MADE. BUBBLE OR HIGHLIGHT ALL REVISED DETAILS AND DRAWINGS ON NEWLY SUBMITTED PLAN SHEETS. IF THESE CORRECTION ITEMS ARE ON STAMPED PAGES THEY WILL REQUIRE THE DESIGN PROFESSIONAL OF THAT DISCIPLINE TO PROVIDE AND STAMP THESE NEW PAGES OF CORRECTIONS.
Please provide a letter addressing the fowling corrections:
? 1. Provide Fault Calcs. For XFMR to main, main to each unit and change to 120 208.
IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT (719) 686-5405, EMAIL ME OR CONTACT DAN , TO DISCUSS THE CONDITIONS OR SET UP AN APPOINTMENT TIME WHEN I CAN BE AVAILABLE TO MEET YOU AT THE COUNTER TO GO OVER THE PLANS.
Dan Wilson Electrical Inspector, Teller County (719) 686-5409 Olya Sharonova Plans Examiner, Teller County | | Electrical | 5631 | Floodplain | Original | A | 5/15/2013 | CORCORANC | CORCORANC | FEMA MAP # 08119C0139D | | Floodplain | 5600 | Zoning/Planning | Original | A | 5/15/2013 | CORCORANC | CORCORANC | CITY APPROVAL FOR BUILDING PERMIT RCVD -- # 13040055 | | Zoning/Planning | 5599 |
|
| |
|