MIKE WELLS CONSTRUCTION CO. | BFR | C | 03/06/2007 | items where corrected from 05-17-06, checked at final (Original code: 03, desc: Struc Frame, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | BFR | C | 32992 |
MIKE WELLS CONSTRUCTION CO. | BSP | R | 12/29/2006 | Trace for expiration of Temp C.O....ljm (Original code: 20, desc: Other, result: , inspector: ) | | | | BSP | R | 160931 |
MIKE WELLS CONSTRUCTION CO. | B= | C | 11/28/2006 | OK for TCO main level CKC (Original code: 04, desc: Struc Final, result: PASS, inspector: MCL) | LANDSITTELM | LANDSITTELM | | B= | C | 34703 |
MIKE WELLS CONSTRUCTION CO. | B= | R | 11/02/2006 | ANSI bathroom, plans, paint gas pipe, city and FD approvalTH CALL MIKE WELLS 641-3400 P.M. (Original code: 04, desc: Struc Final, result: fail, inspector: MCL) | LANDSITTELM | LANDSITTELM | | B= | R | 35514 |
MIKE WELLS CONSTRUCTION CO. | B= | R | 10/10/2006 | Mike was requesting a general look see, not an official inspection final. mechanical rm to be completely drywalled and sealed, all exit lights working properly, accessible bathroom to ANSI standards, city & F.D. approval. (Original code: 04, desc: Struc. Final, result: N/A, inspector: AC) | CHAMBERLINA | CHAMBERLINA | | B= | R | 36237 |
MIKE WELLS CONSTRUCTION CO. | BFR | P | 05/17/2006 | upstairs OK, unfinished lower leveleng cut TJI, block TJI under parallel walls @2', squash blocks end walls, OK to insulate and drywall upstairs. (Original code: 03, desc: Struc. Frame, result: part, inspector: MCL) | LANDSITTELM | LANDSITTELM | | BFR | P | 40561 |
MIKE WELLS CONSTRUCTION CO. | BFR | R | 05/16/2006 | eng on cut TJI, roll blocks one side, FHAs onload bearing walls, nail guards squash blocks on end walls, block @ 24 oc walls parrallel to TJIs, (Original code: 03, desc: Struc. Frame, result: fail, inspector: MCL) | LANDSITTELM | LANDSITTELM | | BFR | R | 40608 |
MIKE WELLS CONSTRUCTION CO. | BSP | C | 05/16/2006 | requesting lath inspection early am (Original code: 20, desc: Other, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | BSP | C | 40577 |
MIKE WELLS CONSTRUCTION CO. | BUL | C | 03/23/2006 | (Original code: 43, desc: Ice & Water Shield, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | BUL | C | 41977 |
MIKE WELLS CONSTRUCTION CO. | BUL | R | 03/20/2006 | too much snow to verify ML/AM (Original code: 43, desc: Ice & Water Shield, result: fail, inspector: MCL) | LANDSITTELM | LANDSITTELM | | BUL | R | 42075 |
MIKE WELLS CONSTRUCTION CO. | BSP | C | 03/16/2006 | (Original code: 21, desc: Deck Piers, result: pass, inspector: AL) | CHAMBERLINA | CHAMBERLINA | | BSP | C | 42113 |
MIKE WELLS CONSTRUCTION CO. | BSH | C | 03/14/2006 | CKC-AM ROOF/ WALLS (Original code: 24, desc: Sheathing, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | BSH | C | 42199 |
KNOP CONSTRUCTION | BFN | C | 02/07/2006 | REQUEST A.M. (Original code: 02, desc: Struc. Foundation, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | BFN | C | 42980 |
MIKE WELLS CONSTRUCTION CO. | BFT | C | 01/26/2006 | Recd. open hole CKC (Original code: 01, desc: Footing /Open Hole, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | BFT | C | 43238 |
MIKE WELLS CONSTRUCTION CO. | BSP | R | 01/01/1900 | 11/16/2006 Recieved an approval from City of W.P. for release of temp C/O until 2/13/07 for 2nd floor only (Original code: 20, desc: Other, result: N/A, inspector: AC) | CHAMBERLINA | CHAMBERLINA | | BSP | R | 152797 |
HOOK ELECTRIC COMPANY, LLC | E= | C | 10/10/2006 | ckc (Original code: 08, desc: Elec. Final, result: PASS, inspector: RKD) | DRUMR | DRUMR | | E= | C | 36238 |
HOOK ELECTRIC COMPANY, LLC | E= | R | 09/11/2006 | CKC two of the condensers required # 8 wire, and were wired in 10, also frogeye in back did not have the batteries connected, rkd (Original code: 08, desc: Elec. Final, result: fail, inspector: RKD) | DRUMR | DRUMR | | E= | R | 37130 |
HOOK ELECTRIC COMPANY, LLC | ES | C | 07/19/2006 | 1, add brass tags to meter cans, 2, bond the 200 amp disconnects, rkd (Original code: 06, desc: Elec. Permanent, result: pass, inspector: RKD) | DRUMR | DRUMR | | ES | C | 38827 |
HOOK ELECTRIC COMPANY, LLC | EUG | C | 07/13/2006 | (Original code: 31, desc: Electrical Trench, result: pass, inspector: RKD) | DRUMR | DRUMR | | EUG | C | 38996 |
HOOK ELECTRIC COMPANY, LLC | ER | C | 05/03/2006 | TH For upstairs only, rkd (Original code: 07, desc: Elec. Rough, result: pass, inspector: RKD) | DRUMR | DRUMR | | ER | C | 40866 |
BUSCH MANNS MECHANICAL, LLC | H= | C | 11/28/2006 | Also Air Conditioning (Original code: 14, desc: Heat Final, result: PASS, inspector: MCL) | LANDSITTELM | LANDSITTELM | | H= | C | 34706 |
LANDMARK PLUMBING & HEATING | HI | C | 05/18/2006 | (Original code: 12, desc: Gas Line Bldg, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | HI | C | 40502 |
LANDMARK PLUMBING & HEATING | HI | R | 05/17/2006 | no test PSI (Original code: 12, desc: Gas Line Bldg, result: fail, inspector: MCL) | LANDSITTELM | LANDSITTELM | | HI | R | 40562 |
LANDMARK PLUMBING & HEATING | HI | R | 05/16/2006 | not done PARTIAL INSP TH (Original code: 12, desc: Gas Line Bldg, result: fail, inspector: MCL) | LANDSITTELM | LANDSITTELM | | HI | R | 40585 |
BUSCH MANNS MECHANICAL, LLC | HV | C | 04/26/2006 | TH (Original code: 16, desc: Vents/Ducts, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | HV | C | 41107 |
LANDMARK PLUMBING & HEATING | P= | C | 11/28/2006 | CKC (Original code: 11, desc: Plumb Final, result: PASS, inspector: MCL) | LANDSITTELM | LANDSITTELM | | P= | C | 34705 |
LANDMARK PLUMBING & HEATING | PTO | C | 05/16/2006 | TH 2ND FLOOR (Original code: 10, desc: Plumb. T/O & Supp, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | PTO | C | 40596 |
LANDMARK PLUMBING & HEATING | PB | C | 03/17/2006 | TH (Original code: 09, desc: Plumb. Base, result: pass, inspector: MCL) | LANDSITTELM | LANDSITTELM | | PB | C | 42101 |